Presentation
Controller ACD20 is prewired with sensor connection box for 2 sensors and is intended for control of mixing valve and circulation pump. It features advanced multi-lingual user interface to setup controller with parameters.
- Boiler return-pipe temperature or any other energy source temperature control.
- Heating or cooling system supply temperature control.
Features
- 2 pre-set hydraulic schemes.
- Prewired with temperature sensor.
- Single sensor option.
- Adjustable temperature control.
- Simple user interface.
- Direct installation onto 20 different mixing valves.
- The possibility to configure the mixing valve opening direction.
- Innovative connector system for connecting sensors.
Outlined functions
Clutch for manual operation
Quick installation
Setup buttons
Plug-in connectors
Acd Graphic display
Technical data
| Tehnični podatki | ACD20 |
|---|---|
| TFT display | ![]() |
| Keypad | ![]() |
| Own consumption | Maximum 3.5 W |
| Standby power consumption | Maximum 0.5 W |
| Torque | 5 Nm |
| Rotation angle | 90 < ° |
| Rotation speed | 2 min 90 < ° |
| Mixing valve control | 3-point PID |
| Circulation pump control | 2-point (ON/OFF) |
| Relay output | electronic relay, 1 (1) A ~, 250 V~ |
| Connection voltage | 230 V ~, 50 Hz |
| Maximum own consumption | 5 W |
| Power supply of built-in clock | Battery CR1025 (Li-Mn) 3 V |
| Accuracy of built-in clock | +/-1 s (24 h) at 20 °C |
| Degree of protection | IP42 according to EN 60529 |
| Safety class | I according to EN 60730-1 |
| Type of temperature sensors | Pt1000 |
| Housing material | PC - dark grey |
| Operating temperature | 0÷50 °C |
| Storage temperature | -20÷65 °C |
| Product weight | 1.000 g |
| Number of pieces in a package unit | 12 pieces |
| Dimensions | ![]() |
| Electrical connection | ![]() |
Performance comparison
| ACD10 | ACD20 | |
|---|---|---|
| Application | ||
| Boiler return-pipe temperature or any other energy source temperature control | ![]() | ![]() |
| Heating or cooling system supply temperature control | ![]() | ![]() |
| Technical features | ||
| No. of preset hydraulic schemes | 2 | 3 |
| Number of electronic relays | — | 1 |
| No. of temperature sensor inputs | 1 | 2 |
| Temperature setup option 10 to 90 °C | ![]() | ![]() |
| Additional sensor for measuring the source temperature | — | ![]() |
| Heating system protection | ||
| Overheating protection | ![]() | ![]() |
| Undercooling protection | ![]() | ![]() |
| Antiblock function for mixing valve | ![]() | ![]() |
| Antiblock function for pump | — | ![]() |
| Data display | ||
| Display of notifications and warnings about the heating system operation | ![]() | ![]() |
| Display of temperatures and other operating data | ![]() | ![]() |
| Detailed display of temperatures for the current day | — | ![]() |
| Review of temperature data for the previous week | — | ![]() |
| Signalling of the mixing valve rotating direction | ![]() | ![]() |
| Control and signalling of the circulation pump operation | — | ![]() |
| Remote access | ||
| Possibility of USB connection to a PC | ![]() | ![]() |
| Setup and installation | ||
| Wizard for an easy and quick device start-up | ![]() | ![]() |
| 14-language user interface | — | ![]() |
| Connection box for sensors | — | ![]() |
| Setting up the operation by selecting the hydraulic scheme | ![]() | ![]() |
| Setting of the rotation direction of the mixing valve | ![]() | ![]() |
| Logging and display of changes made to the setup | — | ![]() |
| Option for retrieval of the basic setup in the event of data loss or unwanted changes | ![]() | ![]() |
| Suitable for installation on different types of mixing valves | ![]() | ![]() |
| "Click" type installation system | ![]() | ![]() |
| Prewired temperature sensor | ![]() | — |
| Sensors with a connector for a “Plug & Play” installation | — | ![]() |
| Power cord equipped with plug | ![]() | ![]() |
Complementary products
-